製冷劑溫度壓力對照表

2021-03-06 製冷世界

大家好,我是小冷,今天我們又要推出我們的福利了,今天給大家推出的是製冷劑的溫度壓力,方便大家在檢修、製冷系統分析的時候查詢蒸發冷凝溫度。

先給大家普及一些簡單的估算方法:

如下:

冷凝溫度=工況溫度(空氣溫度/水溫)+(8~18)℃

蒸發溫度=工況溫度(空氣溫度/水溫)--(10~20)℃

舉例:

如何判斷製冷系統是否缺少冷媒?

很多人都說看系統的運行壓力,但是新手基本上不知道怎麼看;

很簡單,比如現在室外溫度大概35℃,房間設定溫度27℃;那麼根據上面的經驗,得出:

冷凝溫度=35+10=45℃;

蒸發溫度=27-20=7℃;

當然這些是估值哦。

根據我們下面的列表,很快就可以得出壓縮機運行的高低壓了;

比如是R22冷媒的;

那麼高低壓就是:1.75Mpa左右;

低壓就是:0.6Mpa左右。

如果低壓低於這個值,那要考慮系統是否缺少冷媒了。

好了,下面我們把R22、R23、R404A以及R410A溫度壓力對照表附給大家,

R22壓力壓力壓力飽和溫度Kpa(bar/公斤)(PSI)攝氏度100114.5-41.0911501.521.75-32.077200229-25.1772502.536.25-19.508300343.5-14.6543503.550.75-10.384400458-6.55594504.565.25-3.0754500572.50.123985505.579.753.09076006875.86116506.594.258.46357007101.510.927507.5108.7513.249800811615.4658508.5123.2517.589009130.519.6049509.5137.7521.54710001014523.415105010.5152.2525.216110011159.526.953115011.5166.7528.63412001217430.261125012.5181.2531.839130013188.533.371135013.5195.7534.8614001420336.308145014.5210.2537.719150015217.539.095155015.5224.7540.43716001623241.748165016.5239.2543.029170017246.544.281175017.5253.7545.50618001826146.706185018.5268.2547.882190019275.549.034195019.5282.7550.16420002029051.273205020.5297.2552.361210021304.553.43215021.5311.7554.4822002231955.512225022.5326.2556.527230023333.557.526235023.5340.7558.50824002434859.475245024.5355.2560.427250025362.561.364255025.5369.7562.28826002637763.198265026.5384.2564.095270027391.564.98275027.5398.7565.85228002840666.712285028.5413.2567.561290029420.568.399295029.5427.7569.22630003043570.042R410A壓力壓力壓力飽和溫度Kpa(bar/公斤)(PSI)攝氏度100114.5-51.6231501.521.75-43.327200229-36.9922502.536.25-31.795300343.5-27.3513503.550.75-23.448400458-19.9534504.565.25-16.779500572.5-13.8635505.579.75-11.162600687-8.64256506.594.25-6.27737007101.5-4.04647507.5108.75-1.93380081160.0763818508.5123.251.9939009130.53.82649509.5137.755.58441000101457.2741105010.5152.258.9013110011159.510.471115011.5166.7511.98812001217413.457125012.5181.2514.879130013188.516.26135013.5195.7517.60214001420318.906145014.5210.2520.176150015217.521.414155015.5224.7522.62116001623223.799165016.5239.2524.949170017246.526.074175017.5253.7527.17418001826128.251185018.5268.2529.305190019275.530.338195019.5282.7531.35120002029032.344205020.5297.2533.319210021304.534.276215021.5311.7535.21522002231936.139225022.5326.2537.047230023333.537.939235023.5340.7538.81724002434839.68245024.5355.2540.531250025362.541.368255025.5369.7542.19226002637743.004265026.5384.2543.804270027391.544.592275027.5398.7545.3728002840646.136285028.5413.2546.892290029420.547.638295029.5427.7548.37430003043549.101305030.5442.2549.818310031449.550.525315031.5456.7551.22432003246451.914325032.5471.2552.596330033478.553.27335033.5485.7553.93534003449354.593345034.5500.2555.243350035507.555.885355035.5514.7556.5236003652257.148365036.5529.2557.769370037536.558.383375037.5543.7558.9938003855159.591385038.5558.2560.185390039565.560.773395039.5572.7561.35540004058061.93405040.5587.2562.499410041594.563.063415041.5601.7563.6242004260964.172425042.5616.2564.719430043623.565.259435043.5630.7565.79544004463866.324445044.5645.2566.849450045652.567.368R32壓力壓力壓力飽和溫度Kpa(bar/公斤)(PSI)攝氏度100114.5-51.9091501.521.75-43.635200229-37.3232502.536.25-32.15300343.5-27.7313503.550.75-23.85400458-20.3784504.565.25-17.225500572.5-14.3315505.579.75-11.65600687-9.15036506.594.25-6.80467007101.5-4.59257507.5108.75-2.49758008116-0.506138508.5123.251.3939009130.53.20929509.5137.754.95061000101456.624105010.5152.258.2352110011159.59.7896115011.5166.7511.29112001217412.745125012.5181.2514.153130013188.515.52135013.5195.7516.84714001420318.138145014.5210.2519.395150015217.520.619155015.5224.7521.81316001623222.978165016.5239.2524.116170017246.525.229175017.5253.7526.31718001826127.382185018.5268.2528.425190019275.529.447195019.5282.7530.44820002029031.431205020.5297.2532.395210021304.533.341215021.5311.7534.27122002231935.184225022.5326.2536.082230023333.536.965235023.5340.7537.83424002434838.688245024.5355.2539.529250025362.540.358255025.5369.7541.17326002637741.977265026.5384.2542.769270027391.543.55275027.5398.7544.3228002840645.079285028.5413.2545.828290029420.546.567295029.5427.7547.29630003043548.015305030.5442.2548.726310031449.549.428315031.5456.7550.12132003246450.806325032.5471.2551.482330033478.552.15335033.5485.7552.81134003449353.464345034.5500.2554.11350035507.554.748R404A壓力壓力壓力飽和溫度Kpa(bar/公斤)(PSI)攝氏度100114.5-45.7431501.521.75-36.982200229-30.2682502.536.25-24.747300343.5-20.0173503.550.75-15.855400458-12.1234504.565.25-8.73500572.5-5.61055505.579.75-2.7181600687-0.0172796506.594.252.51937007101.54.91357507.5108.757.182680081169.34118508.5123.2511.4019009130.513.3729509.5137.7515.26210001014517.08105010.5152.2518.831110011159.520.52115011.5166.7522.15312001217423.734125012.5181.2525.266130013188.526.753135013.5195.7528.19814001420329.603145014.5210.2530.971150015217.532.303155015.5224.7533.60316001623234.872165016.5239.2536.111170017246.537.322175017.5253.7538.50618001826139.665185018.5268.2540.8190019275.541.912195019.5282.7543.00120002029044.07205020.5297.2545.118210021304.546.147215021.5311.7547.15722002231948.149225022.5326.2549.124230023333.550.082235023.5340.7551.02424002434851.95245024.5355.2552.862250025362.553.759255025.5369.7554.64126002637755.511265026.5384.2556.366270027391.557.209275027.5398.7558.0428002840658.858285028.5413.2559.664290029420.560.458295029.5427.7561.24230003043562.014305030.5442.2562.775310031449.563.525315031.5456.7564.26532003246464.995325032.5471.2565.714330033478.566.423335033.5485.7567.12234003449367.811345034.5500.2568.49350035507.569.159

版權聲明: 本內容轉自網絡,版權歸原作者所有,因無法獲得原始出處無法標明來源敬請諒解,如有侵犯到您的合法權益,請及時在文章後留言說明,我們將儘快處理,對可能產生的任何影響我們均不承擔責任,並且也不代表製冷世界的觀點和立場。

1、新風系統施工工藝
2、電線平方計算與選擇方法
3、風冷冷庫和水冷冷庫哪個好!
4、閉式冷卻塔工作原理圖!
5、風口風速總匯!
6、不懂空氣能熱泵原理?這三張圖夠清晰!
7、多聯機安裝與調試,簡單明了
8、風管阻力計算方法
9、電線平方計算與選擇方法
10、徹底消除冰庫發生的冰塞故障


相關焦點

  • 常用製冷劑溫度壓力對照表
    R22製冷劑溫度壓力對照表溫度℃絕對壓力kpa溫度℃絕對壓力Kpa溫度℃絕對壓力Kpa溫度℃絕對壓力Kpa溫度℃絕對壓力Kpa-41100-172747622311224552176-40105-162858642321256562230-39110-152969661331289572274
  • 製冷劑溫度壓力對照表大匯總!
    R22的單位容積和氨製冷劑差不多。R22可以通過雙級壓縮或空調製冷系統中,製取的最低溫度可達-80℃,但不經濟。R22製冷劑的溫度壓力對照表R410a是由R32和R125兩種工質按50%和50%的質量分數混合而成的HFCs類製冷劑。
  • 常用製冷劑大匯總,附17種製冷劑的溫度壓力表
    R22製冷劑的溫度壓力對照表R410a是由R32和R125兩種工質按50%和50%的質量分數混合而成的HFCs類製冷劑。R410a製冷劑不可燃,ODP為 0,全球變暖係數值GWP為2340,所以R410a並不是真正的環保製冷劑。
  • 你要的製冷劑特點和溫度壓力表,都給你找齊了!
    R32製冷劑的溫度壓力對照表R717(氨)製冷劑的溫度壓力對照表R134a製冷劑的溫度壓力對照表R290製冷劑的溫度壓力對照表R23溫度壓力對照表
  • 汽車空調冷媒壓力標準,汽車空調製冷劑壓力多少是標準
    目前汽車空調充注新型環保R134a製冷劑,是九十年代開始使用的品種,由於不含氯分子對臭氧層沒有破壞作用,對汽車空調系統的改動較少,被聯合國有關組織推薦使用,在粵港等地被稱為「環保雪種」,現在國內外新車的空調系統都使用了環保R134a製冷劑。下面就和電動邦小編一起圍觀汽車空調冷媒壓力標準吧。
  • 製冷劑溫度傳感器故障有什麼表現
    【太平洋汽車網】製冷劑溫度傳感器故障,首先表現為製冷劑溫度傳感器失靈沒有製冷劑溫度信號, 其會在故障存儲器內存儲一條記錄。其中一個傳感器損壞時系統無法確定製冷劑緩慢損耗。因此,製冷循環迴路洩漏時可能導致空調壓縮機因潤滑不足而損壞。
  • 製冷劑影響冷庫溫度 循環量不足導致耗能增加
    製冷劑是影響冷庫溫度的一個重要因素,節流閥調節不當或堵塞,會直接影響到進入蒸發器的製冷劑流量。因此要注意製冷劑的狀態。當冷庫節流閥開啟度過大時,製冷劑流量偏大,蒸發壓力和蒸發溫度也隨之升高,庫房溫度下降速度將減緩;同時,當節流閥開啟度過小或堵塞時,製冷劑流量也減小,系統的製冷量也隨之減小,庫房溫度下降速度同樣將減緩。一般可通過觀察蒸發壓力、蒸發溫度及吸氣管的結霜情況來判斷節流閥製冷劑流量是否合適。節流閥堵塞是影響製冷劑流量的重要因素,引起節流閥堵塞的主要原因是冰堵和髒堵。
  • pt100對照表,PT100鉑熱電阻溫度與電阻值對照表
    打開APP pt100對照表,PT100鉑熱電阻溫度與電阻值對照表 發表於 2017-10-26 09:03:23 在編輯醫療、電機、工業、溫度計算、衛星、氣象、阻值計算等高精溫度設備,應用範圍非常之廣泛。   它的技術參數為三線、四線或兩線 Pt100/Cu50熱電阻信號直接輸入;精度、線性度誤差等級: 0.2級(相對溫度);內置線性化處理和長線補償電路;電源、信號。
  • 快速教你如何給汽車空調的製冷劑充電
    讓我們來看看加注空調製冷劑的方法和過程:空調系統壓力檢查:關閉歧管壓力表的高低壓手動閥,將歧管壓力表上的高低壓軟管與空調系統的高低壓檢修閥接口連接。如果空調系統壓力正常,低壓側歧管壓力表讀數應為0.3MPa左右,高壓側歧管壓力表讀數應為1.5MPa左右。如果不正常,就需要修理。
  • 汽車空調製冷劑多久需要加一次?
    一般情況下,經過一個夏天的消耗之後,汽車空調製冷劑需要一年添加一次。空調製冷劑不足不僅容易造成環境汙染,還會對汽車空調壓縮機造成損耗,增加車主維護車輛的費用和時間。今天就給大家說說如何檢測自己的車子需不要加注空調製冷劑,以及如何為車子加注空調製冷劑。如何檢測自己的車子需不要加注空調製冷劑。
  • pt100溫度傳感器阻值,pt100溫度與阻值對照表
    打開APP pt100溫度傳感器阻值,pt100溫度與阻值對照表 發表於 2017-10-25 16:52:54   Pt100在用於溫度傳感器時,是採用溫度係數符合特定要求的金屬鉑製成的,依據物體電阻值隨溫度變化而變化的原理工作的,電阻式溫度傳感器中,按照國際溫標(國際組織對熱力學溫度的定義)在熱力學溫度為273.15K(0℃)時阻值為100Ω的,由國際電工委員會(IEC)推薦的,傳感器(鉑熱電阻)分度號。
  • 快速教你掌握汽車空調製冷劑加注方法
    歧管壓力表空調系統壓力檢查:關閉歧管壓力表的高、低壓手動閥,將歧管壓力表上的高、低壓力軟管分別與空調系統的高、低壓檢修閥接口相連,若空調系統壓力正常,歧管壓力表讀數應為低壓側0.3MPa左右,高壓側1.5MPa左右。
  • 最全面製冷劑的知識,必須收藏!
    在冷凝器中, 製冷劑溫度為恆定的 37℃。製冷劑從氣體變成液體,放出冷凝潛熱。同時,從冷卻塔來的 30℃ 水進入冷凝 器,溫度升高到 35℃ 。蒸發器中的過程相似。這樣,蒸發器中的製冷劑為恆定的 5℃。製冷劑從液體變成氣體,吸收蒸氣潛熱。冷凍水以 12℃ 進入蒸發器,下降到 7℃ 。蒸發器或冷凝器中的壓力是給定溫度所對應的飽和壓力。這可以從製冷劑壓力溫度表中查出。
  • 超低溫制冷機製冷劑價格一直飛漲你知道嗎
    液態變成氣態必須從外界吸收熱能才能實現,因此是吸熱過程,液態製冷劑蒸發汽化時的溫度叫做蒸發溫度,凝結是指蒸汽冷卻到等於或低於飽和溫度,使蒸汽轉化為液態。蒸發器和回油管的設計必須考慮回油避免頻繁啟動定期除霜及時補充製冷劑以及及時更換易損部件如軸承等維護措施也有助於回油,    安裝在管道上時其水銀或精球應在管道基線上套管的感溫端應朝向流體運動方向壓力表高壓容器和管道應配備兆帕的壓力表中低壓容器和管道應配備兆帕的壓力表感溫燈泡安裝在距離冷水機吸水管的直管上冷凍機器與擠出機配套冷卻的冷水機稱為擠出機冷水機、超低溫制冷機缺相和反向裝置電機過載裝置高低壓裝置缺水自動報警裝置溫度過低防冰裝置線圈過熱裝置水流裝置不足全自動溫度控制系統根據冷卻介質的不同冷凝器可分為水冷式風冷式和蒸髮式
  • 如何利用Excel快速計算製冷劑的物性?
    : 公式二:通過壓力計算溫度: a1,a2,a3的數值參考下表: ,我們就很容易得到R32製冷劑壓力-溫度的計算公式了。 我們同理來擬合下P-T壓力溫度曲線試試:
  • 鹹寧市鋼塑複合管國標壓力對照表
    鹹寧市鋼塑複合管國標壓力對照表 ,「mf21kj1m2r」   鹹寧市鋼塑複合管國標壓力對照表,塗塑複合鋼管螺紋連接的密封問題,燃氣內外塗塑複合鋼管為三層的內外塗塑鋼管,第層是重改性環氧樹脂,外層是噴敷產品噴敷均勻,質量優異,外表美觀。
  • 判斷空調是否要加製冷劑的三種方法
    判斷空調是否要補加製冷劑的方法通常有以下三種:  一、電流法:用鉗形電流表監測室外機工作電流(包括壓縮機和風扇電流),若電流值基本符合銘牌標稱的額定電流,說明製冷劑合適;若低於額定值太多,則製冷劑太少,需補加。
  • 製冷系統充灌製冷劑
    接通電冰箱電源,壓縮機運轉,壓力表指示的壓力慢慢下降,降到一定數值不再下降,這個壓力就是製冷系統的低壓壓力,也就是蒸發器內液態製冷劑的蒸發壓力。一般蒸發壓力控制在0.6~0.8公斤/平方釐米,相應的蒸發溫度為-19~-15℃。低壓壓力的高低是由充灌製冷劑的多少決定的。
  • 製冷劑的命名、分類及應用特性
    一、製冷劑的分類   按製冷劑的分子結構:分為無機化合物和有機化合物兩大類   按製冷劑的組成:單一製冷劑和混合製冷劑   按製冷劑的物理特性:高溫(低壓)、中溫(中壓)、低溫(高壓)製冷劑   下表為按物理特性區分的主要製冷劑:
  • 製冷劑大匯總,你想要了解的製冷劑都在這裡!
    14、R141b(二氯一氟乙烷)  二氯一氟乙烷CH3CCl2F,HCFC-141b,分子量116.95,沸點32.05℃,臨界溫度204.5℃,臨界壓力4.25MPa,破壞臭氧潛能值(ODP)為0.11,全球變暖係數值(GWP)為0.09。